Mounted With Pneumatic or Electric Actuators

With Complete Installation of Actuators
with S/S Mounting Bracket
with Extension Shaft (Stem)
with Double Acting Pneumatic Actuator
with Spring Return Pneumatic Actuator
with Electric Actuator (3 Phase, 240V)
Worm-Gear Operation
Double Acting Actuator (DA):
Counter-clockwise output operation is achieved by inserting
pressure into Port 'A', to force the pistons apart thus rotating
the actuator pinion counter clockwise. During its operation, air
from the outer chamber is exhausted through Port 'B'.
Clockwise output operation is achieved by reverse of the
above and inserting pressure into Port 'B'.
Data Required for Actuator Sizing:
1. Valve torque min. 25% Safety recommended
2. Double acting or Spring-return operation
3. Minimum available operating pressure
Selection of Double Acting Actuators (DA):
Determine the requirement valve torque, this should include 25% safety margin and the minimum.
  Operating pressure available. Refer to the pressure/torque table and select the minimum pressure
  column applicable.
Follow this column down until a value not less than that required is found. Next read across to the
  left hand column and read the model number to be ordered.
Example: valve torque 80Nm plus 25% =100Nm, Minimum operating pressure 5 bar. By reading
  down the 5-bar column afigure. Below 119Nm is 123Nm the model number therefore shown in the
  left hand column is AP4DA.
Remarks: the chosen torque valve, which fixes the type of actuator, has never to be lower than
the requested torque of the valve.
Spring Return Actuators (SR):
Pressure applied to Port 'A' will cause the inner chambers
to be pressurized, forcing the pistons outward to compress
the springs. The pinion is rotated counter-clockwise. Upon
release of pressure through Port 'A' the springs will exert
pressure to closed the pistons and rotate the pinion clockwise
rapidly. This action will often be used to close a 90 deg. turn
valve in shutdown mode.
Determine the required valve torque (this shoudl include 25% safety margin), and the minimum operating
pressure available. Select from the "Spring Stroke/"0 deg." table a value that is not less than the
required valve torque (including safety margin). Next refer to the pressure table and select under your min.
pressure and "0 deg." torque column a figure not les than that required. (including Safety Margin)
Example: Valve torque 60 Nm plus 25% = 75Nm. Checking the "Spring Stroke/"0 deg." column, it will
be noted the nearest value is 108 Nm. By following the line across to the vertical 5 bar "0 deg." torque
column , a figure of 109 Nm is shown therefore, the suitable actuator is AP5SR5. In a normal valve shut-
down situation the actuator would operate the valve to break out a less than 108 Nm. If "0 deg." torque
at operating pressure is at operating pressure is too low, continue down the column until an acceptable
value is found, compare with the corresponding "Spring Stroke/"0 deg." column to ensure that this
also is adequate. This model may be used.